Get More Info!

Announcement
Announcement
Developing a dynamic model using TRNSYS for cold store cooling load calculation

Student name: Mr Paintamilselvan M S
Guide: Dr Ramkishore Singh
Year of completion: 2012
Host Organisation: Centre for Research, Technology and Innovation, Thermax India Ltd.
Supervisor (Host Organisation): Mr D P Navale
Abstract: A transient simulation model is developed for calculating the cooling load in a small scale cold storage under development. This model predicts the temperature of the commodity in storage at every time step in turn associated product load, transmission heat gain, and electrical gain using TRNSYS software. The transient product load calculation is carried out in MS Excel tool and linked with TRNSYS platform. The product load consists of sensible load, respiration and transpiration load. Standard Half cooling time or 7/8 cooling time values are used in calculation. Multi zone building tool (TRNBuild) used to calculate gains and Google SketchUp 8 tools are linked with simulation studio. Weather file of study location is loaded and hourly simulation results are studied for cooling demand, commodity temperature, relative humidity and respective air node temperature. Typically in a multi commodity cold storage, the refrigeration load peak largely depends on loading pattern of commodity. This model is aimed to assist a designer to arrive at optimum sizing and operating parameters of refrigeration systems.